Solar PV Earthing & Earth Conductor Size Calculator (AS/NZS)
Size the earth conductor and module-frame bonding for an Australian residential PV array per AS/NZS 5033:2021 and AS/NZS 3000 Table 5.1. Free copper / aluminium lookup.
Solar PV Earthing / EGC Size Calculator
How to use this calculator
Enter the active conductor cross-section of your PV DC string in mm², select copper or aluminium, and the calculator returns the minimum earth conductor size per AS/NZS 3000 Table 5.1 (referenced from AS/NZS 5033:2021 § 5.3). The same value applies to the bonding jumper between module frames and the rack-to-MEN earth conductor.
Inputs:
- Active conductor cross-section (mm²) — the DC string conductor area. A typical Australian 6.6 kW or 10 kW residential rooftop install uses 6 mm² PV1-F or H1Z2Z2-K solar cable. Larger 13 kW or 15 kW systems may step up to 10 mm² for VD on long roof-to-inverter runs.
- DC overcurrent protection (A) — the touch-safe DC fuse in the array isolator. Used for the lug torque guidance.
- Earth conductor material — copper for nearly every CEC-accredited install. Aluminium is permitted at 16 mm² and larger but rarely used due to corrosion concerns at outdoor terminations.
- Mechanically protected run — if the earth is in conduit or duct, minimum cross-section drops to 2.5 mm². Unprotected runs require 4 mm² minimum.
How the math works (AS/NZS 3000 Table 5.1)
Table 5.1 sizes the earth conductor from the active cross-section:
S (active) ≤ 16 mm² → Earth = S (same as active)
16 < S ≤ 35 mm² → Earth = 16 mm²
S > 35 mm² → Earth = S / 2
Aluminium earth conductors are uprated by approximately 1.5× to match copper conductivity. CEC PV install guidelines add a 6 mm² minimum for arrays even when the table would allow smaller.
Worked example. A 6.6 kW Perth rooftop array has two strings of 10 modules at 11 A Imp each, into a single-MPPT 5 kW inverter. DC active conductors are 6 mm² H1Z2Z2-K (rated 70 A free air / 41 A in conduit). Table 5.1 gives Earth = 6 mm² copper. CEC minimum is also 6 mm². The 6 mm² green/yellow earth conductor runs alongside the DC pair through the roof, into the inverter, and on to the MEN bar at the main switchboard.
If the array uses 10 mm² actives for a long 30 m roof-to-inverter run (VD upsize), Table 5.1 still gives 10 mm² earth (because 10 ≤ 16 mm²). The continuity test from farthest module frame to MEN bar should read ≤ 1.0 Ω.
AS/NZS 5033:2021 earthing requirements
AS/NZS 5033:2021 is the PV-specific installation standard. The earthing clauses you actually use:
- § 5.3.1 — every exposed conductive part of the PV system bonded via a protective earth conductor.
- § 5.3.2 — earth conductor sized from AS/NZS 3000 Table 5.1 (active cross-section based).
- § 5.3.3 — minimum 6 mm² copper from PV rack to main earthing terminal.
- § 5.3.4 — no separate auxiliary earth electrode for the PV array.
- § 5.4 — DC functional earthing rules (different from protective earthing — only applies to transformer-isolated inverters, which are now rare).
CEC accreditation audits specifically check § 5.3.3 (the 6 mm² minimum) and the < 1.0 Ω continuity test result. Failing either is grounds for STC rebate clawback under the CER’s PV inspection program.
Module-frame bonding hardware in Australia
CEC-accredited installers use one of three approaches:
- WEEB-Lug-6.7 or AS-Earthing-Pin (Wiley Electronics / Clenergy) — stainless toothed washers that bite through the anodising. Cheapest and most common at $0.50-$0.80 per module wholesale. Compatibility matrix on the rack manufacturer’s website (Clenergy, Sunlock, K2, Schletter).
- Integrated earthing rail — Clenergy PV-Earth-IRail, Schletter EcoFoot 2+ with FixZ pins, IronRidge XR1000 (imported via BayWa). The rail itself provides the UL 2703 / IEC 61730 listed grounding path.
- Discrete M6 stainless earth lugs and bare 6 mm² copper jumper — old-school but still acceptable for retrofits on legacy frames without listed bonding clips.
All three are acceptable under AS/NZS 5033. The CEC Approved Solar Retailer requirements add that the bonding hardware must be on the published compatibility list of the module manufacturer (Trina Vertex S, JinkoSolar Tiger Neo, REC Alpha Pure-R, Q-CELLS Q.PEAK DUO ML-G11 all publish compatibility tables).
When voltage drop forces an earth upsize
AS/NZS 3000 keeps domestic VD ≤ 3% on lighting and 5% on power circuits. CEC PV practice limits DC VD to 1% from string to inverter and AC VD to 2% from inverter to main switchboard. On a long 30+ m roof-to-inverter run, the actives often jump from 6 mm² to 10 mm² for VD. Under Table 5.1 the earth conductor follows — 6 mm² becomes 10 mm² to stay at full active cross-section.
Use the solar panel voltage calculator to check VD before sizing the earth.
Common Australian inspection findings
The five most-common earthing faults flagged by CEC accreditation audits and CER PV inspection program reports:
- Earth conductor under-sized (4 mm² used instead of 6 mm² minimum per AS/NZS 5033 § 5.3.3).
- Module-frame bonding hardware not listed for the specific frame profile.
- No bonding between separate rail sections joined by sliding joints.
- M6 earth lug installed without a toothed washer biting the anodising — passes a visual but fails continuity test at > 5 Ω.
- Earth conductor terminated under a non-UV-rated grommet — degrades within 5 years of summer roof temperatures.
A pre-energisation continuity test from the farthest module frame to the MEN bar catches all five — should read ≤ 1.0 Ω before energising the AC isolator.
Stand-alone (off-grid) and battery-coupled systems
Battery-coupled and stand-alone systems add AS/NZS 4509 and AS/NZS 5139 requirements on top of AS/NZS 5033:
- DC bus earthing must be functional (not protective) — typically a single midpoint reference to earth via a 100 mA-class fuse.
- Battery enclosure bonded to PV earth via the same earth conductor.
- Lithium battery installations under AS/NZS 5139 require an emergency-stop button on the AC side that also disconnects the DC bus.
The 6 mm² minimum and < 1.0 Ω continuity rules still apply. The bonded chain extends from module frame → rack → DC combiner → inverter → battery enclosure → AC switchboard → MEN bar.
Related calculators
- Solar panel wire size calculator — sizes the actives that drive Table 5.1
- Solar panel voltage calculator — voltage drop on the same conductors
- Solar string sizing calculator — sets the DC fuse rating that drives lug selection
Sources
- AS/NZS 5033:2021 — Installation and safety requirements for PV arrays — primary PV code reference
- AS/NZS 3000:2018+A1:2024 — Wiring Rules — Table 5.1 reference
- Clean Energy Council — PV System Design Guidelines — installer guidance
- CER PV Inspection Program findings — most-common audit faults
- Sunlock + Clenergy + K2 mounting system compatibility matrices — bonding hardware reference