SolarCalculatorHQ

Off-Grid Solar System Calculator (UK)

Free UK off-grid solar calculator. Sizes PV array (kWp), battery bank (kWh), and inverter (kW) from daily kWh load using PVGIS irradiance data and MCS-aligned design factors.

Off-Grid Solar System Calculator

PV array (kW DC)
3 kW
Usable battery energy (kWh)
18 kWh
Battery bank (kWh nameplate)
21.1 kWh
Inverter (kW continuous)
3.8 kW

How to use this calculator

The UK off-grid calculator above takes your daily kWh load and PVGIS-derived peak sun hours and returns three numbers: PV array size in kWp DC, battery bank capacity in kWh nameplate, and inverter continuous kW rating. All values are in metric / SI units and align with MCS MIS 3002 sizing methodology.

  1. Daily energy use (kWh) — your average daily AC load. Pull it from a recent Ofgem-regulated supplier bill (monthly kWh ÷ 30) or sum nameplate watts × hours-on. Ofgem’s TDCV (Typical Domestic Consumption Values) puts the medium UK household at 2,700 kWh/year ≈ 7.4 kWh/day electric only. Off-grid UK cottages typically run 4-8 kWh/day because high-draw loads (oven, immersion, heat pump) get swapped for LPG, oil, or wood.
  2. Peak sun hours (h/day) — annual average kWh/m² hitting an optimally tilted module. PVGIS-SARAH3 averages: Cornwall 2.9, London 2.6, Manchester 2.5, Edinburgh 2.4, Inverness 2.3, Stornoway 2.2. Default 2.6 covers southern England; bump to 2.4 for Scotland.
  3. Days of autonomy — UK winter cyclonic weather routinely produces 5-7 days of <30% normal PV output. 3 days minimum for southern England; 4 days for Scotland and the Western Isles. Pair with a 5-7 kVA Honda/Stephill diesel generator for backup.
  4. Battery chemistry — LiFePO₄ (BYD, Pylontech, Fogstar, Solax) is now standard. AGM (Victron, Rolls) still appears in budget Welsh smallholdings but the £/kWh-cycled is poor.
  5. Peak instantaneous load (W) — usual UK suspects: kettle 3,000 W, electric shower (avoid off-grid!) 8,500 W, immersion 3,000 W, washing machine 2,200 W, microwave 850 W. Most UK off-grid systems run a 3-5 kW Victron Multiplus-II continuous.

How the math works

The UK calculator follows the methodology in MCS MIS 3002 (PV system design) extended for stand-alone systems per IEC 62124 and the Energy Saving Trust’s Solar Photovoltaic Systems for Stand-Alone Use guide:

PV array (kWp DC):

kWp = daily_kWh / (peak_sun_hours × derate)

Derate 0.77 covers BS 7671 inverter losses, MPPT charge-controller losses, DC cable losses, soiling, and 2-3% module mismatch — the same Performance Ratio MCS uses for grid-tied UK systems but with the inverter loss applied at the battery side instead of the grid side. With UK defaults of 6 kWh/day at 2.6 PSH: kWp = 6 / (2.6 × 0.77) = 3.0 kWp DC. This typically maps to 7-8× 400 W panels (Trina Vertex S+, JA Solar, Longi Hi-MO X6).

Battery bank (kWh nameplate):

usable_kWh    = daily_kWh × autonomy_days
nameplate_kWh = usable_kWh / (DoD × battery_round_trip_eff)

6 kWh × 3 days = 18 kWh usable; nameplate = 18 / (0.90 × 0.95) = 21.1 kWh of LiFePO₄. That maps to about 4× Pylontech US5000 (4.8 kWh nameplate each) or 1× BYD HVS 22.0.

Inverter (kW continuous):

kW = peak_load_W × 1.25 / 1000

A 3,000 W kettle plus 500 W background load = 3,500 W peak × 1.25 = 4.4 kW. The Victron Multiplus-II 5kVA/48V is the standard answer for UK residential off-grid.

What an off-grid system actually costs in the UK (Q1 2026)

Pulling installed-cost ranges from MyBuilder, Checkatrade, Solar Energy UK members, and Wind & Sun (Ledbury) and Mr Solar (Liphook) off-grid specialists. All prices include the 0% HMRC VAT relief running through March 2027:

System sizePV kWpBattery kWhTotal installedNotes
Cottage / outbuilding1.5-2.58-14 (Li)£8,500-13,500Pylontech + 3 kW Victron
Small full-time off-grid (6 kWh/day)3-418-25 (Li)£14,000-22,000BYD HVS + Multiplus-II 5kVA
Full off-grid house (10 kWh/day)4-625-40 (Li)£22,000-35,000+ Honda 5 kVA generator backup
Croft / smallholding (Highlands & Islands)5-740-60 (Li)£30,000-45,000Sized for 4-day autonomy

Add a wood stove for primary heating and budget £1,200-2,500 for a Stephill or Honda dual-fuel generator (essential north of Manchester for December cover).

Where most UK off-grid systems get under-sized

Three common mistakes from Solar Energy UK and Wind & Sun customer post-mortems:

  1. PVGIS averages used in winter. The 2.6 PSH headline figure is a yearly average; December alone runs 0.8-1.0 PSH. A bank sized to year-round mean will run flat by 2 January. Use either 4-day autonomy at the annual PSH or recompute at the worst-month PSH.
  2. Electric showers and kettles in the load list. Electric showers at 8.5 kW will trip even a 5 kVA inverter on start. Switch to LPG instant-water, gas hob, and gas oven for off-grid; reserve electric for fridge, freezer, lights, electronics, and small AC tools.
  3. Heat pump on solar. UK ASHPs draw 6-8 MWh/year; an off-grid PV array large enough to cover that is wildly uneconomic. Heat with wood/oil/LPG and reserve PV for the small loads.

Pair this with the battery bank calculator, charge-time calculator, and wire-size calculator

This UK off-grid sizing calculator gives the three headline numbers. The battery bank calculator drills into Ah at your chosen system voltage (24 V or 48 V). The charge-time calculator confirms recovery time after a 3-day overcast stretch. The wire-size calculator picks BS 7671-compliant CSA in mm² for the DC runs between array, charge controller, bank, and inverter.

Sources

Frequently asked questions

How much solar do I need to live off-grid in the UK?
For a typical UK off-grid cottage running 6 kWh/day at 2.6 peak sun hours (the southern England average from PVGIS), you need about 3.0 kWp of PV plus 14-18 kWh of LiFePO₄ battery for three days of autonomy. A full UK house at the Ofgem TDCV medium of 2,700 kWh/yr (≈7.4 kWh/day) requires roughly 3.7 kWp PV and 25 kWh battery. Off-grid in Scotland north of about 56° N latitude needs 30-40% more PV than Cornwall to handle short December days.
Why does the UK need more battery than the US for the same load?
British off-grid systems sit under 2.4-3.0 PSH for nine months of the year and 0.8-1.4 PSH in December-January. The PV array generates almost nothing for days at a time during midwinter cyclonic weather, so the design has to lean on battery (3-day autonomy) plus a dual-fuel generator. The Energy Saving Trust's *Stand-Alone Photovoltaic Systems Guide* and MCS MIS 3002 both recommend a minimum 3-day autonomy north of 53° N (Manchester northwards) and 2-3 days south of it.
Does the UK 0% VAT relief on solar apply to off-grid systems?
Yes. The 0% VAT rate on residential energy-saving materials introduced by HMRC in April 2022 (extended to March 2027) applies to PV panels, inverters, and battery storage installed at a domestic dwelling — including off-grid. There's no requirement to be on or near the grid. A £15,000 installed off-grid system therefore stays at £15,000 instead of attracting £3,000 of VAT. Note that the Smart Export Guarantee (SEG) does NOT apply to off-grid systems because there's no grid connection to export to.
Can off-grid solar power an air-source heat pump in the UK?
Technically yes but it's rarely cost-effective. A typical UK ASHP draws 6,000-8,000 kWh/year for space heating plus hot water, which would require roughly an 11-15 kWp PV array and 80-120 kWh of battery to ride through midwinter — easily £45,000-70,000 installed. Most off-grid UK households heat with wood, oil, LPG, or biomass and use solar PV only for lights, fridge, electronics, and small AC loads. The MCS Heat Emitter Guide recommends grid-tied for any electric primary heating.
What inverter brand is best for off-grid in the UK?
The UK off-grid market is dominated by Victron Energy (Multiplus-II, Quattro), Outback Power (Radian, FXR), and Studer Innotec (Xtender) for 48 V residential systems. All three are MCS-listed where required and BS 7671 / G98 / G99 capable for systems with grid-fallback. For pure off-grid (no grid at all) you don't need the G98/G99 certification, which simplifies installation considerably. Sunamp, GivEnergy, and SolarEdge are common on-grid choices but rarer in pure off-grid builds.

Related calculators