SolarCalculatorHQ

Solar Cable Size Calculator (UK)

Free UK solar cable size calculator. Enter voltage, current, and cable run length to get the smallest copper cross-section that stays within BS 7671 voltage-drop limits.

Prepared by the Solar Calculator HQ editorial team. Review our formula, source and limitation standards.

Solar Wire Size Calculator

Smallest wire that meets your spec
12 AWG
Drop at this size: 0.58 V (2.4%)

How to use this calculator

Enter four values:

  1. System voltage — typical UK domestic strings run at 250–600 V DC; 12 V / 24 V / 48 V for leisure and off-grid setups
  2. Current — the maximum amps the circuit will carry (read panel Imp from the data sheet, or charge controller output rating)
  3. One-way length — distance in metres from the array to the inverter or charge controller
  4. Max voltage drop % — 3% is the MCS recommendation, 2% is excellent, 1% is best-in-class

The calculator finds the smallest cable cross-section that keeps drop within your target. Smaller cable is cheaper and easier to install — bigger cable wins only when no smaller size meets your spec.

Why cable sizing matters more than UK installers admit

A cable that’s too small does three bad things on a UK rooftop:

  1. Wastes energy as heat in the conductor
  2. Reduces voltage at the inverter — MPPT trackers can clip, charge controllers can underperform
  3. Heats up under load — sun-baked roof void cables can sit at 60–70°C, accelerating insulation ageing and reducing the 25-year warranty’s real lifespan

Going one cross-section larger than the minimum is one of the cheapest performance upgrades on a DIY install — copper costs scale roughly linearly with cross-section, but loss reductions are exponential.

The voltage-drop math

The calculator tries every standard cross-section (1.5, 2.5, 4, 6, 10, 16, 25 mm²) and computes the voltage drop for your inputs. It picks the smallest cable that meets your maximum drop percentage.

DC voltage drop formula:

V_drop = 2 × Length(m) × Resistance(Ω/m) × Current(A)

The factor of 2 accounts for the round trip — current flows out through the positive conductor and back through the negative. Resistance values come from BS EN 60228 copper tables at 25°C.

Cross-sectionΩ/km @ 25°C
1.5 mm²12.10
2.5 mm²7.41
4 mm²4.61
6 mm²3.08
10 mm²1.83
16 mm²1.15
25 mm²0.727

Each step up roughly drops resistance by 35–40%, which is why moving from 4 mm² to 6 mm² is usually enough to fix marginal drop on UK domestic strings.

Typical UK PV cable sizes

Run length5 A10 A20 A30 A
5 m1.5 mm²2.5 mm²4 mm²6 mm²
10 m2.5 mm²4 mm²6 mm²10 mm²
20 m4 mm²6 mm²10 mm²16 mm²
30 m6 mm²10 mm²16 mm²25 mm²
50 m10 mm²16 mm²25 mm²35 mm²

Assumes 3% max drop on a 48 V DC system. Higher string voltage cuts cable size dramatically — a 600 V string carries the same kW as a 48 V string at one-twelfth of the current, and voltage drop scales with current squared.

Voltage drop versus ampacity — pick the larger size

Two separate constraints govern UK cable choice:

  • Ampacity (current-carrying capacity): the cable must safely carry the load without overheating. Set by BS 7671 Table 4D2 or equivalent, with derating for grouping, ambient temperature and conduit fill.
  • Voltage drop: the cable must keep the load above its minimum operating voltage. Set by your design choice — typically the MCS 3% DC recommendation.

For long runs from a barn or garage roof, voltage drop usually wins. For short, high-current battery-bank runs, ampacity wins.

Always use the larger of the two requirements. This calculator handles voltage drop only — confirm ampacity with BS 7671 tables or have a competent person verify your design.

BS 7671 and MCS code references

  • BS 7671:2018 Amendment 2 (the 18th Edition Wiring Regulations) — Appendix 4 voltage-drop limits, Table 4D2 cable ampacity
  • BS EN 50618 — DC PV-rated cable (H1Z2Z2-K) specification
  • MCS Standard MIS 3002 — installation requirements for grid-connected PV
  • IET Code of Practice for Grid-Connected Solar PV Systems — design guidance and connection requirements

The Energy Saving Trust and Solar Energy UK both publish design guides aligned with these standards. DNOs increasingly request a written voltage-drop calculation as part of G98/G99 connection paperwork.

What it costs to get cable wrong

A 4 kWp UK domestic system installed under MCS in 2026 typically costs £6,500–£8,500 turnkey including 0% VAT under the current ZER scheme (Energy Saving Trust survey, MCS Installation Database, MyBuilder and Checkatrade quotes). Annual generation is around 3,400–3,800 kWh. A persistent 4% voltage drop above the 3% target costs roughly 40 kWh/year — about £14/year at the 2026 Ofgem price cap of 27 p/kWh. Across a 25-year warranty that’s around £350.

Compare that to the cost of upsizing 30 m of 4 mm² to 6 mm² — about £45–£70 in materials at UK trade prices. Cable upgrades almost always pay back several times over.

For grid-connected installations, only an MCS-certified installer can register your system for the Smart Export Guarantee (SEG) and submit DNO G98/G99 paperwork. Always demand a written cable-sizing calculation as part of the system design pack before commissioning.

Frequently asked questions

What cable size do I need for a 4 kWp UK solar system?
For a typical 4 kWp domestic string at ~600 V DC and 8 A, 4 mm² copper cable handles cable runs up to about 25 m within the MCS 3% DC voltage drop recommendation. Long roof-to-inverter runs over 30 m, or 12/24 V leisure-battery setups, often need 6 mm² or 10 mm². Always run the numbers — the right answer depends on your voltage and length.
What does BS 7671 require for solar cabling?
The 18th Edition Wiring Regulations (BS 7671:2018+A2:2022) Appendix 4 sets a maximum 5% voltage drop from origin to the furthest point on power circuits and 3% on lighting. For PV, MCS Standard MIS 3002 recommends staying below 3% on the DC side and 3% on the AC side. Cable must also be sized for ampacity per the regulations, separately from voltage drop — the larger of the two requirements wins.
Can I use ordinary twin and earth for solar?
No. Indoor T&E (6242Y) is fine for AC-side runs from the inverter to the consumer unit but is not approved for DC PV strings or anywhere exposed to sunlight. Use BS EN 50618 PV-rated cable (often labelled H1Z2Z2-K) for module string runs — it's UV-stable, tolerates 90°C continuously, and is the only cable a competent MCS installer will use on the DC side.
Is bigger cable always better?
It cuts losses and runs cooler, but copper is expensive and 16 mm² or 25 mm² is a pain to terminate at standard MC4 connectors and inverter input blocks. Use this calculator to find the smallest cross-section that meets your 3% target — that's the cost-optimal answer. If you're close to a threshold, sizing up one step is usually cheap insurance for a 25-year MCS-warranted system.

Related calculators