SolarCalculatorHQ

Solar Cable Size Calculator (UK)

Free UK solar cable size calculator. Enter voltage, current, and cable run length to get the smallest copper cross-section that stays within BS 7671 voltage-drop limits.

Solar Wire Size Calculator

Smallest wire that meets your spec
12 AWG
Drop at this size: 0.58 V (2.4%)

How to use this calculator

Enter four values:

  1. System voltage — typical UK domestic strings run at 250–600 V DC; 12 V / 24 V / 48 V for leisure and off-grid setups
  2. Current — the maximum amps the circuit will carry (read panel Imp from the data sheet, or charge controller output rating)
  3. One-way length — distance in metres from the array to the inverter or charge controller
  4. Max voltage drop % — 3% is the MCS recommendation, 2% is excellent, 1% is best-in-class

The calculator finds the smallest cable cross-section that keeps drop within your target. Smaller cable is cheaper and easier to install — bigger cable wins only when no smaller size meets your spec.

Why cable sizing matters more than UK installers admit

A cable that’s too small does three bad things on a UK rooftop:

  1. Wastes energy as heat in the conductor
  2. Reduces voltage at the inverter — MPPT trackers can clip, charge controllers can underperform
  3. Heats up under load — sun-baked roof void cables can sit at 60–70°C, accelerating insulation ageing and reducing the 25-year warranty’s real lifespan

Going one cross-section larger than the minimum is one of the cheapest performance upgrades on a DIY install — copper costs scale roughly linearly with cross-section, but loss reductions are exponential.

The voltage-drop math

The calculator tries every standard cross-section (1.5, 2.5, 4, 6, 10, 16, 25 mm²) and computes the voltage drop for your inputs. It picks the smallest cable that meets your maximum drop percentage.

DC voltage drop formula:

V_drop = 2 × Length(m) × Resistance(Ω/m) × Current(A)

The factor of 2 accounts for the round trip — current flows out through the positive conductor and back through the negative. Resistance values come from BS EN 60228 copper tables at 25°C.

Cross-sectionΩ/km @ 25°C
1.5 mm²12.10
2.5 mm²7.41
4 mm²4.61
6 mm²3.08
10 mm²1.83
16 mm²1.15
25 mm²0.727

Each step up roughly drops resistance by 35–40%, which is why moving from 4 mm² to 6 mm² is usually enough to fix marginal drop on UK domestic strings.

Typical UK PV cable sizes

Run length5 A10 A20 A30 A
5 m1.5 mm²2.5 mm²4 mm²6 mm²
10 m2.5 mm²4 mm²6 mm²10 mm²
20 m4 mm²6 mm²10 mm²16 mm²
30 m6 mm²10 mm²16 mm²25 mm²
50 m10 mm²16 mm²25 mm²35 mm²

Assumes 3% max drop on a 48 V DC system. Higher string voltage cuts cable size dramatically — a 600 V string carries the same kW as a 48 V string at one-twelfth of the current, and voltage drop scales with current squared.

Voltage drop versus ampacity — pick the larger size

Two separate constraints govern UK cable choice:

  • Ampacity (current-carrying capacity): the cable must safely carry the load without overheating. Set by BS 7671 Table 4D2 or equivalent, with derating for grouping, ambient temperature and conduit fill.
  • Voltage drop: the cable must keep the load above its minimum operating voltage. Set by your design choice — typically the MCS 3% DC recommendation.

For long runs from a barn or garage roof, voltage drop usually wins. For short, high-current battery-bank runs, ampacity wins.

Always use the larger of the two requirements. This calculator handles voltage drop only — confirm ampacity with BS 7671 tables or have a competent person verify your design.

BS 7671 and MCS code references

  • BS 7671:2018 Amendment 2 (the 18th Edition Wiring Regulations) — Appendix 4 voltage-drop limits, Table 4D2 cable ampacity
  • BS EN 50618 — DC PV-rated cable (H1Z2Z2-K) specification
  • MCS Standard MIS 3002 — installation requirements for grid-connected PV
  • IET Code of Practice for Grid-Connected Solar PV Systems — design guidance and connection requirements

The Energy Saving Trust and Solar Energy UK both publish design guides aligned with these standards. DNOs increasingly request a written voltage-drop calculation as part of G98/G99 connection paperwork.

What it costs to get cable wrong

A 4 kWp UK domestic system installed under MCS in 2026 typically costs £6,500–£8,500 turnkey including 0% VAT under the current ZER scheme (Energy Saving Trust survey, MCS Installation Database, MyBuilder and Checkatrade quotes). Annual generation is around 3,400–3,800 kWh. A persistent 4% voltage drop above the 3% target costs roughly 40 kWh/year — about £14/year at the 2026 Ofgem price cap of 27 p/kWh. Across a 25-year warranty that’s around £350.

Compare that to the cost of upsizing 30 m of 4 mm² to 6 mm² — about £45–£70 in materials at UK trade prices. Cable upgrades almost always pay back several times over.

For grid-connected installations, only an MCS-certified installer can register your system for the Smart Export Guarantee (SEG) and submit DNO G98/G99 paperwork. Always demand a written cable-sizing calculation as part of the system design pack before commissioning.

Frequently asked questions

What cable size do I need for a 4 kWp UK solar system?
For a typical 4 kWp domestic string at ~600 V DC and 8 A, 4 mm² copper cable handles cable runs up to about 25 m within the MCS 3% DC voltage drop recommendation. Long roof-to-inverter runs over 30 m, or 12/24 V leisure-battery setups, often need 6 mm² or 10 mm². Always run the numbers — the right answer depends on your voltage and length.
What does BS 7671 require for solar cabling?
The 18th Edition Wiring Regulations (BS 7671:2018+A2:2022) Appendix 4 sets a maximum 5% voltage drop from origin to the furthest point on power circuits and 3% on lighting. For PV, MCS Standard MIS 3002 recommends staying below 3% on the DC side and 3% on the AC side. Cable must also be sized for ampacity per the regulations, separately from voltage drop — the larger of the two requirements wins.
Can I use ordinary twin and earth for solar?
No. Indoor T&E (6242Y) is fine for AC-side runs from the inverter to the consumer unit but is not approved for DC PV strings or anywhere exposed to sunlight. Use BS EN 50618 PV-rated cable (often labelled H1Z2Z2-K) for module string runs — it's UV-stable, tolerates 90°C continuously, and is the only cable a competent MCS installer will use on the DC side.
Is bigger cable always better?
It cuts losses and runs cooler, but copper is expensive and 16 mm² or 25 mm² is a pain to terminate at standard MC4 connectors and inverter input blocks. Use this calculator to find the smallest cross-section that meets your 3% target — that's the cost-optimal answer. If you're close to a threshold, sizing up one step is usually cheap insurance for a 25-year MCS-warranted system.

Related calculators