Solar Wire Size Calculator (Canada)
Free Canadian solar wire size calculator. Enter voltage, current, and run length to get the smallest AWG that stays within CSA C22.1 voltage drop limits for PV circuits.
Solar Wire Size Calculator
How to use this calculator
Enter four values:
- System voltage — Canadian residential strings typically run at 250–600 V DC; off-grid cabin and RV systems use 12 V, 24 V or 48 V
- Current — maximum amps the circuit will carry (panel Imp from the data sheet, or charge controller output rating)
- One-way length — distance in feet from the array to the inverter or charge controller
- Max voltage drop % — 3% is the typical CEC industry recommendation for DC strings, 2% is excellent
The calculator finds the smallest AWG that keeps drop within your target. Smaller wire is cheaper at Canadian copper prices and easier to terminate in standard MC4 connectors and CSA-listed combiner boxes.
Why wire sizing is critical for Canadian solar
Canadian arrays face two specific challenges that magnify the cost of undersized wire:
- Long runs are common — many rural and cottage installations run from a ground-mount or barn-roof array to a house several hundred feet away
- Cold pushes string voltage up but low irradiance keeps current modest — meaning the worst-case ampacity event (winter Voc spike) and worst-case voltage drop (summer Imp at full sun) happen at different times of year, both of which the design must handle
Going one AWG larger than the bare minimum is one of the cheapest performance upgrades on a Canadian DIY install — copper costs scale linearly, but loss reduction is exponential.
The voltage drop math
The calculator tries every standard AWG (14, 12, 10, 8, 6, 4, 2, 1/0) and computes the voltage drop for your inputs. It picks the smallest wire (highest AWG number) that meets your maximum drop percentage.
V_drop = 2 × Length(m) × Resistance(Ω/m) × Current(A)
The factor of 2 accounts for the round-trip — current flows out through the positive conductor and back through the negative. Resistance values come from CEC Table D3 and CSA C22.1 standard copper at 75°C operating temperature.
| AWG | Ω/km @ 75°C |
|---|---|
| 14 | 8.45 |
| 12 | 5.31 |
| 10 | 3.34 |
| 8 | 2.10 |
| 6 | 1.32 |
| 4 | 0.83 |
| 2 | 0.52 |
| 1/0 | 0.33 |
Each AWG step roughly drops resistance by 37%, which is why moving from 10 AWG to 8 AWG cuts marginal voltage drop on cabin and rural Canadian strings.
Typical Canadian PV wire sizes
| Run length | 5 A | 10 A | 20 A | 30 A |
|---|---|---|---|---|
| 10 ft | 14 AWG | 14 AWG | 12 AWG | 10 AWG |
| 25 ft | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
| 50 ft | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
| 100 ft | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
| 200 ft | 6 AWG | 4 AWG | 2 AWG | 1/0 |
Assumes 3% max drop on a 24 V DC system. Higher string voltage cuts wire size dramatically — at 500 V DC the same kW carries about one-twentieth of the current at 24 V, and voltage drop scales with current squared.
Voltage drop versus ampacity — pick the larger size
CEC Section 4 sets ampacity with derating:
- Ampacity — the wire must safely carry continuous current. Derate for ambient (CEC Table 5A), grouping in conduit (Table 5C), and the 1.25× continuous-duty factor that applies to PV source circuits per Rule 64-210
- Voltage drop — the wire must keep the load above its minimum operating voltage
For long ground-mount or remote-cabin runs, voltage drop usually wins. For short, high-current battery-bank cables, ampacity wins. Always use the larger of the two requirements. This calculator handles voltage drop — confirm ampacity with CEC Table 2 (allowable ampacity for not more than three copper conductors in raceway) and apply derating.
CSA and CEC code references
- CSA C22.1 (Canadian Electrical Code, 2024) — master Canadian electrical installation standard
- CSA C22.2 No. 271 — PV-rated cable specification (RPV)
- CEC Section 64 — solar photovoltaic systems
- CEC Rule 8-102 — voltage drop allowances
- CEC Rule 64-200 — cold-weather voltage adjustment for PV
NRCan and CanmetENERGY publish design guidance aligned with these standards. Your provincial AHJ (ESA in Ontario, Technical Safety BC, Régie du bâtiment in Québec, etc.) requires a CSA-stamped permit and inspection — the inspector will check both ampacity and voltage drop calculations as part of the rough-in inspection.
What it costs to get wire wrong in Canada
A typical 7 kW Canadian residential rooftop system installed in 2026 costs CAD 18,000–28,000 turnkey before incentives (Canada Greener Homes Grant data, NRCan benchmark studies, HomeStars and Solar Industry Magazine quotes). Annual generation is around 7,500–9,500 kWh depending on province. A persistent 2% voltage drop above the 3% target costs roughly 150 kWh/year — about CAD 22/year at the 2026 Canadian residential average of 14.5 cents/kWh. Across a 25-year warranty that’s around CAD 550.
Compare that to the cost of upsizing a 100 ft run from 8 AWG to 6 AWG — about CAD 75–110 in materials at Canadian wholesaler prices. Upsizing pays back many times over.
Related solar calculators
- Solar voltage drop calculator — full CEC voltage drop calculation
- Solar panel tilt calculator — Canadian latitude and snow-shedding tilt
- Solar panel orientation calculator — south versus east-west yield
- Solar charge time calculator — battery charging from PV
For grid-tied systems, your provincial utility (Hydro One, BC Hydro, Hydro-Québec etc.) requires a permit-stamped electrical drawing and CSA-certified installer sign-off before energizing. Always demand a written cable-sizing calculation as part of the design pack — it protects you on both warranty and inspection day.