SolarCalculatorHQ

Solar Fuse Size Calculator

Size DC fuses for any PV string, battery bank or inverter. Free solar fuse size calculator using Isc and continuous-current NEC 690.9 rules.

Solar Fuse Size Calculator

Recommended fuse
16 A
PV string (Isc × 1.56) → required ≥ 15.6 A → next standard size 16 A
Reference: NEC 690.9(B) / IEC 60364-7-712

How to use this calculator

Pick the circuit type first — the sizing factor depends on it:

  1. PV string / module — fuse rated at 1.56 × Isc per NEC 690.9(B)
  2. Battery → inverter / load — fuse rated at 1.25 × continuous current
  3. Inverter DC input — fuse rated at 1.25 × max continuous input current
  4. Charge controller output — fuse rated at 1.25 × rated continuous output

Enter your current value, then round up to the next standard fuse size. The calculator does this rounding for you using the NEC 240.6 / IEC 60269 standard ratings list (1, 2, 3, 5, 6, 8, 10, 12, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63, 70, 80, 90, 100 A and up).

Why 1.56× for PV strings — the math behind NEC 690.9(B)

Two separate de-rating factors stack on the DC side of a solar array:

  • 125% for continuous duty. NEC defines a continuous load as one that runs for three hours or more. A PV array on a sunny day clearly qualifies. All continuous-duty circuits require an overcurrent device rated at 125% of the load.
  • 125% for PV irradiance enhancement. Cloud-edge effects and high-altitude irradiance can push a module’s effective Isc 20–25% above the STC nameplate value. NEC bakes another 1.25 multiplier into the PV equation to cover this real-world headroom.

Multiply: 1.25 × 1.25 = 1.5625, which NEC writes as 156%. A module rated 10.5 A Isc requires a fuse of at least 10.5 × 1.56 = 16.4 A → round up to 20 A (next standard NEC size).

Where each fuse goes — circuit-by-circuit

A typical DIY off-grid or hybrid solar system has three or four distinct fused circuits:

  1. PV combiner (one fuse per string) — only required if you have 3+ strings in parallel per the string sizing of your array. For 1–2 strings, the wire ampacity protects the cable on its own.
  2. PV array → charge controller — protect the cable run, usually 1.56× Isc total combined array current.
  3. Charge controller → battery — 1.25× the controller’s rated output current.
  4. Battery → inverter — the big one. A Class T fuse sized at 1.25× the inverter’s continuous DC input current, mounted within 18 inches of the battery positive terminal per NEC 706.30(C).

Each fuse must be DC-rated for at least the open-circuit voltage of that part of the system. PV-side fuses must handle up to 1000 V DC (residential) or 1500 V DC (commercial). Battery-side fuses on a 48 V system need at least 80 V DC rating with adequate interrupt capacity (Class T is the typical choice — 20,000 A IR is standard).

Standard fuse sizes (NEC 240.6)

When the calculation produces a fractional answer like 16.4 A, you round up to the next listed standard size. The standard NEC fuse ratings are:

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A

Smaller fuses below 15 A are also standardized (1, 2, 3, 5, 6, 8, 10, 12) for module-level applications and microinverter trunk cables. Above 250 A, sizes step up to 300, 350, 400, 500 A and beyond for utility-scale combiners.

You never round down. Rounding down means the fuse can nuisance-trip under normal operating current — it’s both unsafe (premature failure) and a NEC violation.

Picking the fuse type — gPV vs Class T vs ANL

Three families of DC fuse dominate residential and small-commercial solar:

  • gPV (IEC 60269-6) — designed specifically for PV string protection. 1000 V DC or 1500 V DC rating, low pre-arcing energy, fast clearing under fault conditions. Standard for combiner-box use. Brands: Mersen Helio Protect, Bussmann PV.
  • Class T (UL 248-15) — extremely high interrupting capacity (20 kA at 160 V DC), fast-acting, typical for battery-to-inverter circuits. The standard choice for 12/24/48 V battery banks where fault current is enormous.
  • ANL / MIDI / MEGA — slower-blow, lower interrupt rating. Acceptable for DC loads under 32 V where prospective short-circuit current is moderate. Common in RV and marine. Not appropriate for large lithium battery banks — use Class T instead.

The calculator gives you the amperage; you still pick the fuse type based on voltage and prospective fault current.

Worked examples

Example 1 — PV string fuse. Module Isc = 11.2 A, 2 modules in series, 3 strings in parallel.

Required fuse ≥ 11.2 × 1.56 = 17.5 A → standard 20 A gPV at 1000 V DC, one per string in the combiner.

Example 2 — Battery to inverter. 48 V battery bank, 5000 W inverter, 92% efficiency.

Continuous DC current = 5000 / (48 × 0.92) = 113 A Fuse ≥ 113 × 1.25 = 141 A → standard 150 A Class T fuse near the battery terminal.

Example 3 — Charge controller output. 60 A MPPT controller charging a 24 V battery bank.

Fuse ≥ 60 × 1.25 = 75 A → standard 80 A Class T or DC breaker between the controller and the battery.

Voltage drop and fuse choice are separate constraints

Don’t confuse a fuse with wire sizing. The fuse protects the wire and equipment from sustained over-current and short-circuit faults. Voltage drop sizing protects system efficiency by minimizing resistive losses.

Standard practice on the DIY off-grid side:

  1. Size the wire for ≤3% voltage drop at full load.
  2. Size the fuse at 1.25× (or 1.56× on the PV side) of continuous current.
  3. Confirm the fuse rating does not exceed the wire’s ampacity — if it does, upsize the wire.

For grounded systems also check your equipment grounding via the solar grounding calculator — the equipment ground conductor must be sized to safely clear the largest expected fault, which is usually the fuse’s interrupt rating.

When to call an electrician

DIY-friendly: small RV and off-grid systems under 48 V DC, single-string roof installs, prefab plug-and-play kits.

Licensed electrician territory: anything tying to the utility grid, anything in conduit penetrating a roof or wall, 1000+ V DC strings, lithium battery banks above 5 kWh, and any installation in a jurisdiction that requires permits or inspections (most US states). The calculator gives the right fuse size, but final installation must comply with the local AHJ — and on the grid side, that means a licensed electrician’s stamp.

Limitations and disclaimer

This calculator implements the NEC 690.9 / 706.30 sizing rules for North American installations. International readers — IEC 60364-7-712 (Europe), AS/NZS 5033 (Australia/NZ), and CSA C22.1 Section 64 (Canada) use the same 1.56 factor for PV string sizing but may use different standard fuse ratings (e.g. 16 A is a standard IEC size but not a standard UL size). Round up to the nearest standard size available in your market.

Always confirm fuse selection against the equipment manufacturer’s maximum overcurrent device rating — printed on the module sticker, the inverter spec sheet, and the charge controller manual. The lower of (NEC calc, manufacturer spec) wins.

Frequently asked questions

Why multiply Isc by 1.56 for PV string fuses?
NEC 690.9(B) requires PV string overcurrent devices to be rated at least 156% of the module's short-circuit current. The 1.56 factor is 1.25 (for continuous-duty loading) × 1.25 (for elevated PV irradiance enhancement above STC). The factor only applies to the PV source side — battery, inverter, and load-side circuits use a 1.25× factor instead.
Do I need a fuse on every string or just on the combiner?
If two or more strings are paralleled, NEC 690.9(A) requires overcurrent protection on each string unless the module short-circuit current is below the module's series fuse rating. With three or more strings in parallel, a fault in any one string can be back-fed by the other strings — that's the reason for per-string fusing in a combiner box.
What's the difference between a PV fuse and a regular fuse?
PV fuses are rated for DC (1000–1500 V DC typically), have a gPV time-current characteristic that tolerates the steady operating current of a string while clearing short-circuits quickly, and are tested per UL 248-19 or IEC 60269-6. A standard AC household fuse will not safely interrupt a PV DC arc and must never be used.
Can I use a circuit breaker instead of a fuse?
Yes — a DC-rated circuit breaker sized the same way (1.56× Isc on the PV side, 1.25× continuous current on battery and inverter sides) is acceptable per NEC 690.9. Make sure the breaker is rated for the system DC voltage and interrupting current. Most household AC breakers cannot safely interrupt DC fault current and are not interchangeable.
Do I need a fuse between the battery and the inverter?
Yes. Battery banks can deliver thousands of amps into a short circuit. Class T or ANL fuses sized at 1.25× the inverter's continuous DC input current, with a DC interrupt rating that exceeds the battery's short-circuit current, are the safe choice. NEC 706.30 and most inverter manuals require this protection within 18 inches of the battery terminal.

Related calculators

📋 Embed this calculator on your site (free, attribution required)

Free to embed on any non-commercial or commercial site, provided the attribution link remains visible. No tracking, no email capture, just the calculator.